Physical data 3 Phase

Outdoor unit RAV-SP1104AT8-E / AT7 RAV-SP1404AT8-E / AT7 RAV-SP1604AT8-E / AT7
4 HP 5 HP 6 HP
Air Flow m3/h - l/s 6060 - 1683 6180 - 1717 6180 - 1717
Sound pressure level dB(A) C 49 51 51
Sound power level dB(A) C 66 68 68
Operating range °C C -15 / 46 -15 / 46 -15 / 46
Sound pressure level dB(A) H 50 52 53
Sound power level dB(A) H 67 69 70
Operating range °C H -20 / 15 -20 / 15 -20 / 15
Dimensions (HxWxD) mm 1340 x 900 x 320 1340 x 900 x 320 1340 x 900 x 320
Weight kg 95 95 95
Compressor type DC Twin Rotary DC Twin Rotary DC Twin Rotary
Flare connections
Gas in 5/8 5/8 5/8
Liquid in 3/8 3/8 3/8
Minimum pipe length m 3 3 3
Maximum pipe length m 75 75 75
Maximum height difference m 30 30 30
Chargeless pipe length m 30 30 30
Power supply V-ph-Hz 380/415-3N-50 / 380-3N-60 380/415-3N-50 / 380-3N-60 380/415-3N-50 / 380-3N-60
C = cooling mode
H = heating mode
Electrical Data for 60Hz Model could vary slightly, please refer to technical databook for specifics details.
The specification may be subject to change without notice for purpose of improvement.